| Specifications | FX2N-32CCL | |
| Module type | Remote station | |
| Link points per station | I/O points | 32 |
| Register | 8 | |
| Max. number of I/O points | — | |
| Number of connectable modules | — | |
| Power supply | 5 V DC | Max. 130 mA (from base unit) |
| 24 V DC | 50 mA | |
| Related I/O points | 8 | |
| Weight | kg | 0.3 |
| Dimensions (WxHxD) | mm | 43x90x87 |
| Order information | Art. no. | 102961 |
Notes: To connect this module to a FX3UC or FX3GC base unit, an adapter FX2N-CNV-IF or a power supply FX3UC-1PS-5V is required. More informations about CC-Link are available in various other publications from Mitsubishi Electric.
| Specifications | FX3U-CAN | |
| Module type | CANopen master | |
| CANopen communication standard | CiA 301 V4.2, CiA 302 V4.1, CiA 305 V2.2 | |
| CANopen Lift application profile mode | CiA 417 V2.1 | |
| CANopen PLC device profile mode | CiA 405 V2.0 | |
| Max. number of modules that can be connected to the network | 30 without repeater; 127 with repeater | |
| Station numbers | 1–127 | |
| Supported communication speeds | kbps | 10, 20, 50, 125, 250, 500, 800, 1000 |
| Status displays | RUN, error, power, network status | |
| Power supply | 5 V DC | 290 mA |
| 24 V DC | — | |
| Related I/O points | 8 | |
| Weight | kg | 0.2 |
| Dimensions (WxHxD) | mm | 43x90x88.7 |
| Order information | Art. no. | 252845 |
Notes: To connect this module to a FX3UC/FX3GC base unit, an adapter FX2NC-CNV-IF or a power supply FX3UC-1PS-5V is required. For the connection of a FX3U-CAN to a FX5U/FX5UC base unit, a bus conversion module FX5-CNV-BUSC resp. FX5-CNV-BUS is required.
| Specifications | FX3U-32DP | |
| Module type | Slave station | |
| Transmission type | Bus network | |
| Transmission data | Max. 144 bytes | |
| Interface | 9-pin D-SUB for Profibus DP | |
| Max. number of slave stations per configuration | 8 | |
| Communication speed | 5 V DC | Max. 12 Mbit/s |
| Communication distance | 24 V DC | Max. 1200 (depends on communication speed) |
| Communication cable | Profibus cable with 9-pin D-SUB connector | |
| Related I/O points | 8 | |
| Power supply | 24 V DC/145 mA (from base unit) | |
| Weight | kg | 0.2 |
| Dimensions (WxHxD) | mm | 43x90x89 |
| Order information | Art. no. | 194214 |
Note: To connect a FX3U-32DP to a FX3UC/FX3GC base unit, an adapter FX2NC-CNV-IF or a power supply FX3UC-1PS-5V is required.
| Specifications | FX3U-ENET/FX3U-ENET-P502 | FX5-ENET | |
| Applicable for | Base units FX3G, FX3GC, FX3GE, FX3U, FX3UC | Base units FX5U, FX5UC | |
| Protocol | TCP/IP, UDP | ||
| Communication mode | Full-duplex/half-duplex | ||
| No. of simultaneous open connections | 8 | ||
| Fixed buffer communication | 1023 word x 8 | ||
| Communication with mail server | SMTP, POP3 | ||
| Interface | IEEE802.3u (100BaseTX), IEEE802.3 (10BaseT) | ||
| CC-Link IE Field Network Basic | — | Master | |
| Connector | RJ45 | 2xRJ45 | |
| Max. transfer rate | 100 Mbits/s, 10 Mbit/s | ||
| Max. segment length | m | 100 | |
| Cable | CAT5 STP or 3 STP | ||
| Power supply | 5 V DC | — | — |
| 24 V DC | 240 mA (from base unit) | 110 mA (from base unit) | |
| Related I/O points | 8 | ||
| Weight | kg | 0.3 | 0.2 |
| Dimensions (WxHxD) | mm | 55x90x87 | 40x90x83 |
| Order information | Art. no. | 166086/225142 | 409823 |
Note: To connect this module to a FX3UC base unit, an adapter FX2N-CNV-IF or a power supply FX3UC-1PS-5V is required .
| Specifications | FX3U-64DP-M | FX5-DP-M | |
| Applicable for | Base units FX3U, FX3UC | Base units FX5U, FX5UC | |
| Module type | Master station | ||
| Transmission type | Bus network | ||
| Transmission data | 32 byte/slave (normal service mode) 244 byte/slave (extended service mode) | ||
| Interface | Profibus DP (with 9 pole D-SUB connector) | ||
| Max. number of master per configuration | Max. 1 | ||
| Repeaters | 3 | ||
| Max. number of slaves | 64 | ||
| Communications speed | Profibus standard | ||
| Communications distance m | Max. 1200 (depends on communication speed) | ||
| Communication cable | Profibus cable with 9-pin D-SUB connector | ||
| Power supply | 5 V DC | — | |
| 24 V DC | Max. 155 mA (from base unit) | 150 mA (from base unit) | |
| Related I/O points | 8 | ||
| Weight | kg | 0.2 | |
| Dimensions (WxHxD) | mm | 43x90x87 | 40x90x85.3 |
| Order information | Art. no. | 166085 | 409822 |
| Accessories | Profibus connector up to 12 Mbaud: PROFICON-PLUS, art. no. 140008 or PROFICON-PLUS-PG, art. no. 140009 | ||
Notes : The FX3U-64DP-M can be used in combination with a FX3U or FX3UC base unit only. To connect this module to a FX3UC base unit, an adapter FX2NC-CNV-IF or a power supply FX3UC-1PS-5V is required.
| Specifications | FX2N-64DNET | ||
| Module type | Slave (group 2) | ||
| Node type | G2 server | ||
| Station numbers | 0–63 points | ||
| Supported communication speeds | kbps | 125/250/500 | |
| Communication data (open connection) | Master/ slave | No. of connections | 1 connection (group 2) |
| Transfer time-out | 2,000 ms (ACK time-out) | ||
| UCMM client/server | No. of connections | 63/63 (group 1, 3) | |
| Data length | Max. 64 bytes per connection | ||
| Communication data (I/O connection) | Type | Polling, cyclic, change of state | |
| Data length | Max. 64 bytes (fragmentation is possible) | ||
| Module ID code | K 7090 | ||
| Status displays | Power, module status, network status | ||
| Related I/O points | 8 | ||
| Power supply | 5 V DC | 120 mA | |
| 24 V DC | 50 mA | ||
| Weight | kg | 0.2 | |
| Dimensions (WxHxD) | mm | 43x90x87 | |
| Order information | Art. no. | 131708 | |
| Specifications | FX3U-485ADP-MB | |
| Interface | RS485; Modbus® RS485 | |
| Communication speed* | kbps | 0.3–19.2 |
| Max. communication distance | m | 500 |
| Power supply | 5 V DC | 20 mA (from base unit) |
| 24 V DC | — | |
| Related I/O points | 0 | |
| Dimensions (WxHxD) | mm | 17.6x90(106)x74 |
| Order information | Art. no. | 206191 |
* The communication method and communication speed vary depending upon the communication type.
Notes : This adapter module can be connected directly (without special adapter) to a base unit of the FX3GC, FX3GE or FX3UC series. To connect this adapter module to a FX3G, FX3S or FX3U base unit, an adapter is required.
| Specifications | FX2N-232IF | |
| Interface | RS232C with 9 pole D-SUB connector (photocoupler isolation) | |
| Communication speed | kbps | 0.3–19.2 |
| Communication distance | m | Max. 15 |
| Communication cable | Shielded cable | |
| Communication mode | Full duplex | |
| Protocols | Non protocol mode/start stop synchronisation | |
| Send and receive buffer | 512 byte each | |
| Format | 7 or 8 bits, parity none/even/odd, stop bits: 1 or 2 | |
| Power supply | 5 V DC | 40 mA (from base unit) |
| 24 V DC | 80 mA | |
| Related I/O points | 8 | |
| Weight | kg | 0.3 |
| Dimensions (WxHxD) | mm | 55x90x87 |
| Order information | Art. no. | 66640 |
Note: To connect this module to a FX3UC base unit, an adapter FX2NC-CNV-IF or a power supply FX3UC-1PS-5V is required.
| Specifications | FX3U-CAN | |
| Module type | CANopen master | |
| CANopen communication standard | CiA 301 V4.2, CiA 302 V4.1, CiA 305 V2.2 | |
| CANopen Lift application profile mode | CiA 417 V2.1 | |
| CANopen PLC device profile mode | CiA 405 V2.0 | |
| Max. number of modules that can be connected to the network | 30 without repeater; 127 with repeater | |
| Station numbers | 1–127 | |
| Supported communication speeds | kbps | 10, 20, 50, 125, 250, 500, 800, 1000 |
| Status displays | RUN, error, power, network status | |
| Power supply | 5 V DC | 290 mA |
| 24 V DC | — | |
| Related I/O points | 8 | |
| Weight | kg | 0.2 |
| Dimensions (WxHxD) | mm | 43x90x88.7 |
| Order information | Art. no. | 252845 |
Notes: To connect this module to a FX3UC/FX3GC base unit, an adapter FX2NC-CNV-IF or a power supply FX3UC-1PS-5V is required. For the connection of a FX3U-CAN to a FX5U/FX5UC base unit, a bus conversion module FX5-CNV-BUSC resp. FX5-CNV-BUS is required.
| Specifications | FX3U-ENET-ADP | |
| Protocol | TCP/IP | |
| No. of simultaneous open connections | 1 | |
| Interface | IEEE802.3u (100BaseTX), IEEE802.3 (10BaseT) | |
| Connector | RJ45 (to Ethernet), 3 screw terminals (to ground) | |
| Max. transfer rate | 10 Mbit/s, 100 Mbit/s | |
| Cable | CAT5 STP or 3 STP | |
| Power supply | 5 V DC | 30 mA (from base unit) |
| 24 V DC | — | |
| Related I/O points | 0 | |
| Weight | kg | 0.1 |
| Dimensions (WxHxD) | mm | 23x90(106)x81.5 |
| Order information | Art. no. | 248844 |
Notes : This module can be connected directly (without adapter) to a base unit of the FX3GC or FX3UC series. To connect this module to a FX3G, FX3S or FX3U base unit, an adapter is required.
| Specifications | FX2N-32DP-IF-D | ||
| Power supply | 24 V DC (+20 %/-30 %) | ||
| Power consumption | 14 W | ||
| Internal current consumption | 5 V DC/max. 220 mA (from base unit) | ||
| Interface (connectors) | 9-pin D-SUB for Profibus DP, 8-pin Mini-DIN for PC or programming unit FX-10P/FX-20P/FX-30P | ||
| Communicationspeed | 1200 m | kbps | 9.6/19.2/45.45/93.75 |
| 1000 m | kbps | 187.5 | |
| 400 m | kbps | 500 | |
| 200 m | kbps | 1500 | |
| 100 m | kbps | 3000/6000/12000 | |
| Communication distance | m | Max. 1200 (depends on communication speed) | |
| Communication cable | Profibus cable with 9-pin D-SUB connector | ||
| Max. number of controllable I/O points | 256 | ||
| Weight | kg | 0.4 | |
| Dimensions (WxHxD) | mm | 75x98x87 | |
| Order information | Art. no. | 142763 | |