Specifications FX3U-16CCL-M 1 FX5-CCL-MS
Applicable for Base units FX3G, FX3GC, FX3GE, FX3U, FX3UC, FX5U, FX5UC Base units FX5U, FX5UC
Module type Master station Master/Intelligent device station
Link points per station I/O points 32
Register 8
Max. number of I/O points FX3G/FX3GC/FX3GE: 32 x nbr. of stations ≤128 FX3U/FX3UC: 32 x nbr. of stations ≤256 2 768
Number of connectable modules Max. 16 Max. 24
Power supply 5 V DC
24 V DC 240 mA 100 mA
Related I/O points 8
Weight kg 0.4 0.3
Dimensions (WxHxD) mm 55x90x87 50x90x83
Order information Art. no. 248224 312299
  1. To connect these modules to a FX3UC or FX3GC base unit, an adapter FX2N-CNV-IF or a power supply FX3UC-1PS-5V is required.More informations about CC-Link are available in various other publications from Mitsubishi Electric.
  2. Total of I/O points in base unit and extension units within the CC-Link network ≤384.Notes: Please refer to manual for slave functionality.For the connection of a FX3U-16CCL-M to a FX5U/FX5UC base unit, a bus conversion module FX5-CNV-BUSC resp. FX5-CNV-BUS is required.
 
Specifications FX3U-64CCL
Module type Intelligent device station
Link points per station I/O points 128 (Occupying 1 station with octuple expanded cyclic setting)
Register 32 (Occupying 1 station with octuple expanded cyclic setting)
Max. transmission speed 10 Mbps
Related I/O points 8
Power supply 24 V DC 24 V DC/220 mA
Weight kg 0.3
Dimensions (WxHxD) mm 55x90x87
Order information Art. no. 217915
Notes : When attaching the FX3U-64CCL to a FX3UC/FX3GC base unit, the FX2NC-CNV-IF interface converter or the FX3UC-1PS-5V power supply unit is required. More informations about CC-Link are available in various other publications from Mitsubishi Electric. For the connection of a FX3U-64CC to a FX5U/FX5UC base unit, a bus conversion module FX5-CNV-BUSC resp. FX5-CNV-BUS is required.  
Specifications FX5-CCLIEF
Station type Intelligent device station
Communication speed 1 Gbps
Max. number of I/O points RX 384 points, 48 bytes
RY 384 points, 48 bytes
RWr 1024 points, 2048 bytes 1
RWw 1024 points, 2048 bytes 1
Power supply 5 V DC 10 mA
24 V DC 230 mA (external power supply)
Related I/O points 8
Weight kg 0.3
Dimensions (WxHxD) mm 50x90x103
Order information Art. no. 297444
256 points (512 bytes) when the master station is in high-speed mode.  
Specifications FX5-ASL-M
Module type AnyWireASLINK system master module
Max. number of I/O points 384
Number of connectable modules 128
Power supply 5 V DC 200 mA
24 V DC 100 mA
Related I/O points 8
Weight kg 0.2
Dimensions (WxHxD) mm 40x90x83 (97.3 with connector)
Order information Art. no. 312300
 
Specifications FX5-485ADP
Transmission standard Conforming to RS485 and RS422 standards
Communication speed* bps 300/600/1200/2400/4800/9600/19200/38400/57600/115200
Max. communication distance m 1200 m
External device connection method Terminal block
Power supply 5 V DC 20 mA (from base unit)
24 V DC 30 mA (from base unit)
Related I/O points 0
Weight kg 0.08
Dimensions (WxHxD) mm 17.6x106x74
Order information Art. no. 280514
* The communication method and communication speed vary depending upon the communication type.  
Specifications FX5-232ADP
Transmission standard Conforming to RS232C standard
Communication speed* bps 300/600/1200/2400/4800/9600/19200/38400/57600/115200
Max. transmission distance 15 m
External device connection method 9 pole D-SUB connector (male)
Power supply 5 V DC 30 mA (from base unit)
24 V DC 30 mA (from base unit)
Related I/O points 0
Weight kg 0.08
Dimensions (WxHxD) mm 17.6x106x74
Order information Art. no. 280513
* The communication method and communication speed vary depending upon the communication type.  

Mrežni modul za Profibus DP

Specifications FX5-DP-M
Applicable for Base units FX5U, FX5UC
Module type Master station
Transmission type Bus network
Transmission data 32 byte/slave (normal service mode) 244 byte/slave (extended service mode)
Interface Profibus DP (with 9 pole D-SUB connector)
Max. number of master per configuration Max. 1
Repeaters 3
Max. number of slaves 64
Communications speed Profibus standard
Communications distance m Max. 1200 (depends on communication speed)
Communication cable Profibus cable with 9-pin D-SUB connector
Power supply 5 V DC
24 V DC 150 mA (from base unit)
Related I/O points 8
Weight kg 0.2
Dimensions (WxHxD) mm 40x90x85.3
Order information Art. no. 409822
Accessories Profibus connector up to 12 Mbaud: PROFICON-PLUS, art. no. 140008 or PROFICON-PLUS-PG, art. no. 140009

Ethernet mrežni modul

Specifications FX5-ENET
Applicable for Base units FX5U, FX5UC
Protocol TCP/IP, UDP
Communication mode Full-duplex/half-duplex
No. of simultaneous open connections 8
Fixed buffer communication 1023 word x 8
Communication with mail server SMTP, POP3
Interface IEEE802.3u (100BaseTX), IEEE802.3 (10BaseT)
CC-Link IE Field Network Basic Master
Connector 2xRJ45
Max. transfer rate 100 Mbits/s, 10 Mbit/s
Max. segment length m 100
Cable CAT5 STP or 3 STP
Power supply 5 V DC
24 V DC 110 mA (from base unit)
Related I/O points 8
Weight kg 0.2
Dimensions (WxHxD) mm 40x90x83
Order information Art. no. 409823
Note: To connect this module to a FX3UC base unit, an adapter FX2N-CNV-IF or a power supply FX3UC-1PS-5V is required.  

Mrežni modul za EtherNet/IP

Specifications FX5-ENET/IP EtherNet/IP communications FX5-ENET/IP Ethernet communications
Number of ports 1
Number of connectable units 1 module
Applicable engineering tool GX Works3: Ver. 1.050C or later, EtherNet/IP Configuration Tool for FX5-ENET/IP: Ver. 1.00A or later
Protocol type Socket communication
Number of connections 32 2 Total of 32 connections 3
Transmission specification Communication mode Full-duplex Full-duplex/half-duplex
Max. segment lengthm 100 4
Connection cable 5 100BASE-TX 100BASE-TX, 10BASE-T
Power supply 5 V DC
24 V DC 110 mA (from base unit)
Related I/O points 8
Weight kg 0.2
Dimensions (WxHxD) mm 40x90x83
Order information Art. no. 409824
  1. Since the IP address is shared by two ports, only one address can be set.
  2. The total number of connections for Class 3 communications and UCMM communications is 32.
  3. Up to 32 external devices can access one FX5-ENET/IP module at the same time.
  4. For maximum segment length (length between hubs), consult the manufacturer of the hub used.
  5. A straight/cross cable can be used.

Mrežni modul za CANopen

Specifications FX3U-CAN
Module type CANopen master
CANopen communication standard CiA 301 V4.2, CiA 302 V4.1, CiA 305 V2.2
CANopen Lift application profile mode CiA 417 V2.1
CANopen PLC device profile mode CiA 405 V2.0
Max. number of modules that can be connected to the network 30 without repeater; 127 with repeater
Station numbers 1–127
Supported communication speeds kbps 10, 20, 50, 125, 250, 500, 800, 1000
Status displays RUN, Error, Power, Network status
Power supply 5 V DC 290 mA
24 V DC
Related I/O points 8
Weight kg 0.2
Dimensions (WxHxD) mm 43x90x88.7
Order information Art. no. 252845
Notes: To connect this module to a FX3UC/FX3GC base unit, an adapter FX2NC-CNV-IF or a power supply FX3UC-1PS-5V is required. For the connection of a FX3U-CAN to a FX5U/FX5UC base unit, a bus conversion module FX5-CNV-BUSC resp. FX5-CNV-BUS is required.

Mrežni modul za SAE J1939

Specifications FX3U-J1939
Communication standard version SAE J1939
Network node size SAE J1939: 2–30
Communication method Cyclic, acyclic or request driven (user configurable)
CAN layer-2 communication Send and receive
Max. cable length m 5000
Baud rates kbit/s 10, 20, 50, 100, 125, 250, 500, 800, 1000
Power supply 24 V DC/110 mA (from base unit)
Weight kg 0.2
Dimensions (WxHxD) mm 43x90x95
Order information Art. no. 254276
Note: To connect this module to a FX3UC base unit, an adapter FX2NC-CNV-IF or a power supply FX3UC-1PS-5V is required.

Adapteri

Specifications FX5-232-BD FX5-485-BD FX5-422-BD-GOT
Applicable for Base units FX5U Base units FX5U Base units FX5U
Interface RS232C with 9 pole D-SUB connector RS485 RS422 with 8 pole mini DIN connector
Power supply 5 V DC/20 mA (from base unit) 5 V DC/20 mA (from base unit) 5 V DC/20 mA (from base unit)
Related I/O points
Weight kg 0.02 0.02 0.02
Dimensions (WxHxD) mm 38x51.4x18.2 38x51.4x30.5 38x51.4x15.4
Order information Art. no. 280511 280512 280515